PRINCIPAL COOMPONENTS
  • Structure in stainless steel
  • Semi-hermetic compressors
  • Oil protection resistance
  • Differential oil pressostat
  • AP and BP pressostat for compressor
  • Oil manometer for compressors
  • Circuits AC and BP manometer
ON REQUEST
  • Minimum cooling alarm
  • Regulation systems
  • Condensers
  • Differential oil pressostat
  • Oil level regulating system
  • Liquid receiver
  • Inlet and outlet manifold
  • Liquid filters with by-pass taps
  • Anti-acid inlet filters
  • Cooling fans for low temperature compressors head


NORMAL TEMPERATURE
SERIAL
"TN"
COMPRESSORS CAPACITY
W/h
-10 / +45°C
ABSOR.TOT
Kw
CONDENSER
CAPACITY +.10°C
Kcal/h
CV/HP
CF. 7/2 2 7,5 28000 10.8 45000
CF. 10/2 2 10 38300 14.6 61000
CF. 7/3 3 7,5 48000 18.5 75000
CF. 10/3 3 10 57500 21.9 91000
CF. 15/3 3 15 77100 29.9 122000
CF. 7/4 4 7,5 64000 24.7 100000
CF. 10/4 4 10 76600 29.2 12200
CF. 15/4 4 15 102800 39.9 162000


LOW TEMPERATURE
SERIAL
"TN"
COMPRESSORS CAPACITY
W/h
-10 / +45°C
ABSOR.TOT
Kw
CONDENSER
CAPACITY +.10°C
Kcal/h
CV/HP
CF. 5/2 2 5 7700 6.2 16000
CF. 7/2 2 7,5 9750 8.5 22000
CF. 5/3 3 5 11850 10.1 26000
CF. 7/3 3 7,5 14650 12.7 32000
CF. 10/3 3 10 19950 17.8 46000
CF. 5/4 4 5,5 15800 13.5 34000
CF. 7/4 4 7,5 19550 17.0 42000
CF. 10/4 4 10 26600 23.8 58000

TOP



TECHNICAL DATA

Series "CF" cooling station has been realized for cold production particulariy employed in a supermarkets or for one or more cold rooms. "CF" cooling station produces the cold required from varous users (cold rooms, ice banks etc.) this cold is obtained from progressive, partial on total insertion of cooling station compressors. In case of one or more cold rooms at positive (0°C) that negative (25°C) the solution of cooling stations gives the following advantages:

  • Less consumption of electric power due to less start up of plant
  • Always sensible pressures in the system with good values
  • In case of break of one compressor the cold production is guaranted all the same for the various users.
  • A lot of time saving installation expenses and guarantee to customer of functional plant always
  • Rotating of compressors for homogeneous wear of cooling station
  • Never total standstill of cooling station is required for maintenance or breaks of one more compressors. The cooling station can works with only one compressor producing cold untill the repair is finished.

TECHNICAL DESCRIPTION

  • Base in stainless steel painted
  • Regular shock-absorbers
  • Semi-hermetic compressor
  • Cooling fans on compressor head (series BT)
  • Security oil taps
  • Oil separator
  • Oil reserve
  • Oil level regulator every compressor
  • Compensation valve in LT
  • Oil filter
  • Oil protection resistance
  • Oil commutator
  • Compression commutator with flange
  • Antivibrating in compression for every compressor
  • Reserve valve for every compressor
  • Interception ball taps for every compressor
  • Inlet commutator with one or more out
  • Inlet antivibrating for every compressor
  • Inlet dehydrating fliter for every compressor
  • Interception ball taps for every compressor
  • Liquid separators
  • Liquid commutator with tap
  • Liquid receiver with tap
  • Dehydrating filter with solid cartridge
  • Liquid and humidity indicator
  • Tap for filter by-pass
  • High and low pressure pressostat
  • Low pressostat for functioning of step compressores
  • Differential oil pressostat for compressor with oil pump
  • High pressure manometer
  • Low pressure manometer
  • Oil manometer for compressor with oil pump
  • Security taps
  • High pressure pressostat and for partiality condenser fans (on request)

TOP



SERIES TN SERIES BT
Model A
mm
B
mm
C
mm
Weight
Kg
Model A
mm
B
mm
C
mm
Weight
Kg
CF. 7/2 1500 1200 1500 514 CF. 5/2 1500 1200 1500 530
CF. 10/2 1500 1200 1500 623 CF. 7/2 1500 1200 1500 608
CF. 7/3 2000 1200 1500 700 CF. 5/3 2000 1200 1500 720
CF. 10/3 2000 1200 1500 825 CF. 7/3 2000 1200 1500 790
CF. 15/3 200 1200 1500 840 CF. 10/3 200 1200 1500 810
CF. 7/4 2800 1200 1500 990 CF. 4/5 2000 1200 1500 860
CF. 10/4 2800 1200 1500 1050 CF. 7/4 2800 1200 1500 1030
CF. 15/4 2800 1200 1500 1070 CF. 10/4 2800 1200 1500 1030

TOP



REGULATION SYSTEM OF AC&R OIL LEVEL
The regulation system of AG&R oil level saves energy and increases the service life of the compressors.

WORKING SYSTEM
The oil level in the compressor casing must be controlled. The oil regulating system permits this kind of control and in the meantime keeps the oil level in every casing regalar. The regulating system avoids the need of complex equilization circuits. It works with compressors which are different in model and size.

  1. oil separator
  2. oil supply
  3. oil level regulators
On every compressor is installed an oil regulator to control the inner oil level. The common oil supply feeds every regulator and the oil separator feed the oil supply.

TOP